Mercury 3kva Online UPS Single Phase

720,736.00

Mercury 3kva Online UPS Single Phase

720,736.00


Categories: ,

Specifications


Power 10KVA / 7000W
Voltage range 176 ±5VAC~276 ±5VAC,
Frequency 46~54Hz ±0.5Hz, or 56~64Hz ±0.5Hz auto sensing
Input phase Single phase
Power factor ?0.98
Voltage range 220VAC ±1%
Output phase Single phase
Frequency 50Hz ±0.2% (battery mode)
THD < 2% (Linear load); < 6% (non-Linear load)
Overload 105%~130% 10min turn to Bypass mode,
> 130% 1s turn to Bypass mode
Crest factor 3:1 (max)
Waveform Pure sine wave
Transfer time 0ms (AC mode ? Battery mode)
0ms (AC mode ? Bypass mode)
Efficiency ?88%
AC mode 5 cycles turn off inverter, no transfer to Bypass,
provide alarm.
Battery mode 5 cycles turn off inverter, provide alarm.
Bypass mode Input fuse blown or break action.
Battery Model 12V sealed lead acid maintenance free
DC voltage 240VDC
Configuration 20x 12V/8.2AH
Backup time 13min (half load) / 5min (full load)
Charge current 1A (standard unit) / 5A (long time unit)
Recharge time 90% capacity after 8hrs charging
Communication Interface RS232; SNMP (optional)
Parallel Port Parallel availability for redundancy and load sharing up to three unit
LCD Indication Input voltage/frequency; battery voltage; output voltage/frequency; load watt/VA value & percent; inverter temperature; operation mode such as “on batt” or “on bypass”
LED Indication Green: normal operation; Yellow: warning condition
Red: abnormal operation
Noise level ? 55dB
Temperature 0~40?C; 0 ~ 40?C (storage temperature)
Humidity 0~95% (non-condensing)
Altitude < 1500m
Weight Net/Gross

92/107kg (standard unit); 36/51kg (long time unit)

Warranty